Combustible Dust Testing

Laboratory testing to quantify dust explosion & reactivity hazards

Flammable Gas & Vapor Testing

Laboratory testing to quantify explosion hazards for vapor and gas mixtures

Chemical Reactivity Testing

Laboratory testing to quantify reactive chemical hazards, including the possibility of material incompatibility, instability, and runaway chemical reactions

DIERS Methodology

Design emergency pressure relief systems to mitigate the consequences of unwanted chemical reactivity and account for two-phase flow using the right tools and methods

Deflagrations (Dust/Vapor/Gas)

Properly size pressure relief vents to protect your processes from dust, vapor, and gas explosions

Effluent Handling

Pressure relief sizing is just the first step and it is critical to safety handle the effluent discharge from an overpressure event

Thermal Stability

Safe storage or processing requires an understanding of the possible hazards associated with sensitivity to variations in temperature

UN-DOT

Classification of hazardous materials subject to shipping and storage regulations

Safety Data Sheets

Develop critical safety data for inclusion in SDS documents

Biological

Model transport of airborne virus aerosols to guide safe operations and ventilation upgrades

Radioactive

Model transport of contamination for source term and leak path factor analysis

Fire Analysis

Model transport of heat and smoke for fire analysis

Flammable or Toxic Gas

transport of flammable or toxic gas during a process upset

OSS consulting, adiabatic & reaction calorimetry and consulting

现场安全性研究可以帮助识别explosibility and chemical reaction hazards so that appropriate testing, simulations, or calculations are identified to support safe scale up

Mechanical, Piping, and Electrical

Engineering and testing to support safe plant operations and develop solutions to problems in heat transfer, fluid flow, electric power systems

Battery Safety

Testing to support safe design of batteries and electrical power backup facilities particularly to satisfy UL9540a ed.4

Hydrogen Safety

Testing and consulting on the explosion risks associated with devices and processes which use or produce hydrogen

Spent Fuel

Safety analysis for packaging, transport, and storage of spent nuclear fuel

Decommissioning, Decontamination and Remediation (DD&R)

Safety analysis to underpin decommissioning process at facilities which have produced or used radioactive nuclear materials

Laboratory Testing & Software Capabilities

Bespoke testing and modeling services to validate analysis of DD&R processes

Nuclear Overview

Our Nuclear Services Group is recognized for comprehensive evaluations to help commercial nuclear power plants operate efficiently and stay compliant.

Severe Accident Analysis and Risk Assessment

Expert analysis of possible risk and consequences from nuclear plant accidents

Thermal Hydraulics

Testing and analysis to ensure that critical equipment will operate under adverse environmental conditions

Environmental Qualification (EQ) and Equipment Survivability (ES)

Testing and analysis to ensure that critical equipment will operate under adverse environmental conditions

Laboratory Testing & Software Capabilities

Testing and modeling services to support resolution of emergent safety issues at a power plant

Adiabatic safety calorimeters (ARSST and VSP2)

Low thermal inertial adiabatic calorimeters specially designed to provide directly scalable data that are critical to safe process design

Other Lab Equipment (DSC/ARC supplies, CPA, C80, Super Stirrer)

Products and equipment for the process safety or process development laboratory

FERST

Software for emergency relief system design to ensure safe processing of reactive chemicals, including consideration of two-phase flow and runaway chemical reactions

FATE

Facility modeling software mechanistically tracks transport of heat, gasses, vapors, and aerosols for safety analysis of multi-room facilities

Blog

Our highly experienced team keeps you up-to-date on the latest process safety developments.

Process Safety Newsletter

Stay informed with our quarterly Process Safety Newsletters sharing topical articles and practical advice.

Resources

With over 40 years of industry expertise, we have a wealth of process safety knowledge to share.

Recent Posts

Three Critical Oversights That Precede Combustible Dust Incidents

Posted by The Fauske Teamon 02.28.17

By: Tim Cullina, MS. PE, Senior Safety and Environmental Consulting Engineer, Fauske & Associates, LLC
&乌苏拉Malczewski,化学工程师,Fauske &ssociates, LLC

Combustible dust is present across virtually all industries; sometimes as a raw material or final product, other times as an undesired waste. Near misses, fires, and explosions happen every day. Fauske & Associates, LLC has been in the chemical process safety industry for over 36 years; needless to say, we’ve seen a lot: the good, the bad, and the disastrous. A lack of attention to leading safety indicators can result in critical oversights that can precede an incident. Three crucial errors a facility can make regarding dust and their corresponding solutions are summarized in Figure 1 and explained in detail below.

Figure 1 – Summary Three Critical Combustible Dust Errors
and their Corresponding Solutions
UMTC Figure 1.png
1. Unaware of the Hazard

The first sign of a looming dust fire or explosion is simply not being aware of the hazard. Part of this problem is with the naming convention. Dust can mean anything from powder to particulate solids, and it can be a hazard inside as well as outside of the equipment handling it. Wherever a combustible material is processed, smaller, more hazardous particles can be generated. Some materials, such as certain metals, may not be combustible in large sizes but when reduced to fine particulate produce hazardous characteristics.

NFPA 652 puts responsibility on the owner/operator of a facility with potentially combustible dusts to determine whether the materials are combustible or explosible. The absence of previous incidents is not allowed to be used as the basis for deeming a particulate to not be combustible or explosible. If a dust is deemed noncombustible, documentation must be kept indicating so and needs to be re-evaluated when changes to the process occur. Changes that should trigger dust hazard considerations include, but are not limited to, change in raw material (i.e. composition, supplier, particle size), new operating conditions, changes in handling equipment, etc. Evaluations should occur in order to determine how these changes impact the safety measures within the process.

In the past, some clients have contacted us only after an incident or after OSHA inspected their facility. There has been a shift now that the new NFPA 652 standard and NFPA 654 revision have been published. Companies are being proactive by conducting dust hazard analyses (DHAs) to identify and manage the flammable and/or explosive dust hazards in their facility. These updated standards require owner/operators to conduct DHAs on their processes in the next few years.

2. Underestimate the Hazard

The second marker for an imminent dust incident is underestimating the hazard. There are many ways we see facilities and personnel underestimate the hazards associated with combustible particulate. The most common mistake is assuming that a low KStmeans that there is no hazard. As a matter of fact, most of the combustible dust incident case studies investigated by the Chemical Safety Board (CSB) involved St Class 1 (KSt< 200 bar-m/sec) material (Table 1). OSHA National Emphasis Program on Combustible Dusts identifies St Class 1 materials as capable of producing a “weak explosion” but as evidenced by the aftermath of these events, the results can be devastating. [1], [2]

Table 1 – Summary of Completed CSB Case Studies Involving Combustible Dust [1]
UMTC Table 1 rev.png

The KStvalue is the normalized rate of pressure rise; a measure of the relative explosion severity compared to other dusts. The only non-exploding value of KStis 0 bar-m/sec. That being said, explosions aren’t the only combustible hazard that can cause property damage and death. Fires and flash fires claim lives and cause equipment and facility damage and may be under reported depending on their severity. Other important characteristics to determine the material hazards are described in Table 2.

Data from sources such as literature may help you identify if you have a combustible material but should not be used to design mitigation or prevention efforts in your facility. This is because different particle size ranges of the same material can have different ignitability and explosibility characteristics, depending upon many variables such as particle size distribution, shape, and moisture content. Additionally, these variables can change while the material is passing through process equipment. For this reason, published tables of dust explosibility data may be of limited practical value.

To add to the confusion, testing done by OSHA’s laboratory will identify if your material is combustible, however, it does not follow the methodology needed to produce values that can be used for design. Despite the fact that OSHA warns against it, these values have been used by people without clear understanding of their purpose. Therefore, having representative data from your specific process is key to properly addressing the hazards in your facility.

Intentionally or unintentionally, by collecting samples from the wrong location (for example, off the floor) you are doing yourself and your employees a grave disservice. Samples should reflect the smallest particles in the area of analysis; i.e. within the piece of equipment you are trying to protect. Testing material from an inappropriate location can result in underperforming protection equipment which will not save you any money and it won’t save your facility. If you catch this mistake ahead of time, you will likely need to pay for additional testing to get the proper values; if not, you run the risk of installing mitigation or prevention equipment that may not be sized properly to limit the effects of a fire or explosion in your process.

Once you have the right data, it is also important to understand how to use it. Results from your specific sample are used to design and install appropriate equipment and decide other operational precautions. Mitigating combustible dust hazards needs to be comprehensive effort. Partially protecting a process can be just as bad as doing nothing at all.

Table 2 – Recommended Tests for Material Hazard Characterization

TCUM table 2.png
3. Apathy Towards the Hazard

The third sign that a facility is going to have a combustible dust event is apathy towards the hazards by personnel. It may be obvious that there is a problem but “it has always been that way”, “we never had any issues before”, etc. Most commonly, fugitive dust accumulations are the combustible elephant in the room (and on walls and ceiling beams). Warnings of thermal events include employee complaints of electrostatic shock, visible sparks, charred or smoldering product, discoloration of product or equipment, and unexpected or unusual smoking. It is important to realize that one of these may be the only warning sign of an impending fire or explosion.
UMTC Fig 2.png

Without change, employees and management can become complacent towards the problem. Ultimately, this is a systemic problem; the entire company, from top management to operators, needs to prioritize safety culture. The first step to mitigating apathy is training.

前OSHA引用combustible dust is hazard communication. These requirements include proper labeling of hazardous chemical containers, the collection and use of SDSs, and employee training. Workers – including contractors – need to be told that combustible dust is present and be taught how to prevent fires and explosions. Training should include how to recognize and prevent the hazards of the dust in the facility, recognize unsafe conditions, and take preventative action and alert management. Management needs to understand how to take effective action regarding information about the identified hazards and utilize a management of change (MOC) program that investigates the safety implications of changes to processes with combustible materials. Design work needs to be completed in accordance to industry or commodity specific standards. Engineers need to be aware of the hazards associated with combustible particulate solids in order to minimize the risks in the plant and to seek professional expertise when required. Regardless of if it is fugitive or contained within the equipment, combustible dust hazards need to be given the respect they deserve. [3], [4]

Conclusion
Having a process that handles or generates combustible particulates, solids, powders, or dusts requires an ongoing effort to mitigate or prevent the risk of fires and explosions. Personnel must remain vigilant in order to stay safe. Just like other hazardous chemicals, combustible dust requires several engineered and administrative controls in order to protect your employees and business. If you have questions regarding onsite facility assessments, performing testing, or are interested in training, please contact Tim Cullina atcullina@fauske.com630-887-5237 or Ursula Malczewski atmalczewski@fauske.com630-321-4748

References

1. Completed Investigations - Combustible Dust Explosions and Flash Fires. U.S. Chemical Safety Board. Web. , 13 Jan. 2017. .
2. United States. Department of Labor. Occupational Safety and Health Admin. CPL 03-00-008. Combustible Dust National Emphasis Program (Reissued). Washing ton, D.C.:
U.S. Department of Labor, Occupational Safety and Health Administration, 2008.
3. United States. Department of Labor. Occupational Safety and Health Admin. OSHA 3371-08 2009. Hazard Communication Guidance for Combustible Dust. Washing ton, D.C.:
U.S. Department of Labor, Occupational Safety and Health Administration, 2009.
4. Geddie, J. Edgar. A Guide to Combustible Dusts. Raleigh, NC: N.C. Dept. of Labor, Division of Occupational Safety and Health, 2009. Print.

Subscribe to FAI's Quarterly

Topics:Combustible dust,dust hazard,OSHA,NFPA 652,process safety,Management of change,MOC,flash fire,DHA,electrostatic